Key Features

Click image below to download Technical Data Sheet

Ideal for industrial logging

Voltage Range: 300Vrms 

Current Range: 300A

Rogowski Coils fit around 140mm cables

Voltage Accuracy: ±2% of reading (10 bit) within 90Vac - 300Vrms otherwise ±3%. (50/60Hz ±2%)

Current Accuracy: 2% of range, typically

CAT Rating: 1000V CAT III, 600V CAT IV

Recording Period: 1 sec to 60 mins 

Recording Standard: EN50160

Environmental Sealing: IP65 as standard

Size & Weight: Metric - 145x90x45mm & 500g

add to cart success
add to cart success
This product has variants and can only be added to the cart by viewing the product details page.
add to cart success
Submit Request Quote
 * Denotes Required Field.
Name:
 *
Company Name:
Phone:
Email:
 *
Message:
Request Quote
 
EC-2VA
Single Phase Voltage & Current Logger
EC-2VA Data Logger UK
Current Accuracy Graph EC-2VA
Voltage Accuracy Graph EC-2VA
Frequency:
Plug Type:
Environmental Sealing:
£515.00 / $829 inc sensors, leads, software

Buy

Add to cart
Quantity: 

UK/IRL Hire

Cost Per Week: £120.00

No. Weeks:
Hire Start Date:
Return Carriage:

Pricing from $829 | £515 | €669 excluding delivery and taxes

The EC-2VA data logger is used by power distribution companies, facilities management, electrical or site services and maintenance engineers to monitor both voltage and current variations helping them to diagnose any related issues, or to gather data perhaps to make representations to their power supplier. As the product records both voltage and current, users can determine if low voltage is related to high current demands on site, or if the low voltage is being supplied to the site. This logger uses RS-232 communications with the PC, if you do not have an RS-232 (9 pin D) serial port, you will need a USB to RS-232 converter. Note, the Rogowski Coil breaks open at the black joint, allowing it to be placed around cables (of up to 140mm diameter) without having to break the main circuit.

The advantage of the Electrocorder products over most others is that our data loggers constantly sample information (recording the Min, Max and Average) over the set period, many other products only take 'snap shots' of what is going on and can miss 99.9% of the data that is critical to your analysis.

Kit includes data logger, voltage input lead, Rogowski Coil, RS-232 serial lead, Electrosoft software and carry case.

For help watch our Support Video.

Determining product order codes:
To specify your Electrocorder select various codes and enter into the boxes in order to create an accurate product code. For example: EC-2VA-5H-UK-IP65-KIT.



Latest Case Study